IMIT CONTROL SYSTEM
IMIT CONTROL SYSTEM
HYDRAULIC INTERFACE MODULE
WATERLINK WTL6
WATERLINK WTL6 is a hydraulic separation module between
two heat generators powered by different energy sources.
The most typical appliance is that between a thermo-fire-
place (or a thermo-heater) and a gas boiler. When han-
dling heat produced by the biomass source, the module
disables the traditional boiler and activates the 3-way
valve to send hot water to the domestic heating system.
Otherwise the 3-way valve is not enabled, allowing the gas
boiler to meet the required heating needs.
Code
Article
370
181
4
6
0
Supply voltage = 230 V / 50 Hz
Max. absorbed power = 100 W
Water temperature probe = NTC 1 %
Operating water temperature = 0/95°C
Max. water probe temperature = 150°C
Working room temperature = 0/50°C
Storage temperature = 0/60°C
Max. fluid pressure = 3 bar
Protection rating = IPX4D
Certifications = CE
Description
Pack.
561554
WATERLINK WTL6
(1 pump)
Hydraulic module (heating only), with 1 circulator, 1 x 3-way diverter valve,
1 x 34-plate exchanger, complete with cover and FIRE WATER HID control unit.
a.r.
561555
WATERLINK WTL6
(2 pumps)
Hydraulic module (heating only), with 2 circulators, 1 x 3-way diverter valve,
1 x 34-plate exchanger, complete with cover and FIRE WATER HID control unit.
a.r.
WATERCOMBI WTC7
HYDRAULIC INTERFACE MODULE
550
181
6
4
0
WATERCOMBI WTC7 is a hydraulic separation module be-
tween two heat generators powered by different energy
sources, with the production of domestic hot water. The
most typical appliance is that of the combination between
a thermo-fireplace (or a thermo-heater) and a boiler.
When handling heat produced by the biomass source, the
module disables the traditional boiler and sends hot wa-
ter to the domestic heating system or directly to the user
in the event of requesting domestic hot water. Otherwise,
it allows the gas boiler to meet the heating demand and
produce domestic hot water.
Code
Article
Supply voltage = 230 V / 50 Hz
Max. absorbed power = 100 W
Water temperature probe = NTC 1%
Operating water temperature = 0/95°C
Max. water probe temperature = 150°C
Working room temperature = 0/50°C
Storage temperature = 0/60°C
Max. heating fluid pressure = 3 bar
Max. fluid pressure ACS = 6 bar
Protection rating = IPX4D
Certifications = CE
Description
Pack.
S
y
s
t
e
m
s
f
o
r
r
e
n
e
w
a
b
l
e
e
n
e
r
g
y
s
o
u
r
c
e
s
561556
WATERCOMBI
WTC7
(1 pump)
Hydraulic heating and DHW module, with 1 circulator, 1 x 3-way diverter valve,
1 flow switch, 1 x 30-plate exchanger, 1 x 14-plate exchanger, complete with
cover casing and FIRE WATER HID control unit.
a.r.
561557
WATERLINK
WTC7
(2 pumps)
Hydraulic heating and DHW module, with 2 circulators, 1 x 3-way diverter valve,
1 flow switch, 1 x 30-plate exchanger, 1 x 14-plate exchanger, complete with
cover casing and FIRE WATER HID control unit.
a.r.
32