Pumps

Pumps

Calio

31

Calio Z

Rp

DN

Q [m

3

/h]

H [m]

p [bar]

T [°C]

n [rpm]

Rp

DN

Q [m

3

/h]

H [m]

p [bar]

T [°C]

n [rpm]

≥ -10

Data for 50 Hz operation

Also available for 60 Hz

≥ -10

Data for 50 Hz operation

Also available for 60 Hz

1 1/2 - 2

32 - 100

≤ 51

≤ 18

≤ 16

- ≤ +110

≤ 4500

1 1/4

32 - 65

≤ 70

≤ 18

≤ 16

- ≤ +110

≤ 4500

Description:

Maintenance-free high-efficiency flanged or screw-ended glandless pump

with high-efficiency electric motor and continuously variable differential

pressure control.

Applications:

Heating, ventilation, air-conditioning and heat recovery systems, cooling

systems, industrial recirculation systems

http://shop.ksb.com/catalog/k0/en/product/ES000881

Description:

Maintenance-free high-efficiency flanged or screw-ended glandless pump in

twin pump design with high-efficiency electric motor and continuously

variable differential pressure control.

Applications:

Heating, ventilation, air-conditioning and heat recovery systems, cooling

systems, industrial recirculation systems

http://shop.ksb.com/catalog/k0/en/product/ES000913

Description:

Single-stage close-coupled in-line volute casing pump, with PumpDrive

variable speed system and common motor/pump shaft

Applications:

Heating systems, air-conditioning systems, cooling circuits, water supply

systems (not approved for drinking water according to the German

Environment Agency), service water supply systems, industrial recirculation

systems, swimming pools

http://shop.ksb.com/catalog/k0/en/product/ES000925

Description:

Single-stage close-coupled in-line volute casing pump as twin pump, with

PumpDrive variable speed system and common motor/pump shaft

Applications:

Heating systems, air-conditioning systems, cooling circuits, water supply

systems (not approved for drinking water according to the German

Environment Agency), service water supply systems, industrial recirculation

systems

http://shop.ksb.com/catalog/k0/en/product/ES000926

In-line pumps

Etaline L

Etaline DL

Rp

DN

Q [m

3

/h]

H [m]

p [bar]

T [°C]

Rp

DN

Q [m

3

/h]

H [m]

p [bar]

T [°C]

≥ -15

Data for 50 Hz operation

Also available for 60 Hz

≥ -15

Data for 50 Hz operation

Also available for 60 Hz

1 - 1 1/4

32 - 80

≤ 95

≤ 21

≤ 10

- ≤ +120

1 1/4

32 - 80

≤ 150

≤ 21

≤ 10