18/19
0452
0472
0572
FX2-G05 /SL-E
Alimentazione elettrica
PRESTAZIONI
REFRIGERAZIONE (GROSS VALUE)
Potenza frigorifera
Potenza assorbita totale
EER
ESEER
REFRIGERAZIONE (EN14511 VALUE)
Potenza frigorifera
VARIABLE PRIMARY FLOW
0352
0402
0602
0652
0702
0772
V/ph/Hz
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
(1)
(1)
(1)
(1)
(1)(2)
kW
336,3
386,0
kW
97,46
110,7
kW/kW
3,449
3,487
kW/kW
4,640
4,650
kW
335,9
385,6
kW/kW
3,420
3,450
kW/kW
4,500
4,490
439,6
480,9
126,7
142,1
3,470
3,384
4,630
4,630
439,3
480,5
3,440
3,350
4,500
4,490
563,4
610,9
161,2
176,8
3,495
3,455
4,630
4,630
562,9
610,4
3,450
3,420
4,460
4,500
650,6
690,1
187,4
198,1
3,472
3,484
4,640
4,670
650,1
689,5
3,430
3,440
4,490
4,500
748,9
221,9
3,375
4,650
748,3
3,340
4,500
EER
(1)(2)
ESEER
(1)(2)
Classe EUROVENT
EFFICIENZA ENERGETICA
EFFICIENZA STAGIONALE IN RAFFREDDAMENTO (Reg. UE 2016/2281)
Refrigerazione d’ambiente
Prated,c
(7)
SEER
(7)(8)
Rendimento ηs
(7)(9)
SCAMBIATORI
SCAMBIATORE UTENZA IN REFRIGERAZIONE
Portata
(1)
Perdita di carico allo scambiatore
(1)
CIRCUITO FRIGORIFERO
N. compressori
N. circuiti
Carica refrigerante
LIVELLI SONORI
Pressione sonora
(3)
Potenza sonora in refrigerazione
(4)(5)
DIMENSIONI E PESI
A
(6)
B
(6)
H
(6)
Peso in funzionamento
(6)
FX2-G05 /SL-E
Alimentazione elettrica
PRESTAZIONI
REFRIGERAZIONE (GROSS VALUE)
Potenza frigorifera
(1)
Potenza assorbita totale
(1)
EER
(1)
ESEER
(1)
REFRIGERAZIONE (EN14511 VALUE)
Potenza frigorifera
(1)(2)
EER
(1)(2)
ESEER
(1)(2)
Classe EUROVENT
EFFICIENZA ENERGETICA
EFFICIENZA STAGIONALE IN RAFFREDDAMENTO (Reg. UE 2016/2281)
Refrigerazione d’ambiente
Prated,c
(7)
SEER
(7)(8)
Rendimento ηs
(7)(9)
SCAMBIATORI
SCAMBIATORE UTENZA IN REFRIGERAZIONE
Portata
(1)
Perdita di carico allo scambiatore
(1)
CIRCUITO FRIGORIFERO
N. compressori
N. circuiti
Carica refrigerante
LIVELLI SONORI
Pressione sonora
(3)
Potenza sonora in refrigerazione
(4)(5)
DIMENSIONI E PESI
A
(6)
B
(6)
H
(6)
Peso in funzionamento
(6)
Note:
-
-
-
-
-
-
-
-
-
kW
336
386
4,65
4,66
%
183
183
l/s
16,08
18,46
kPa
25,9
34,1
439
480
4,68
4,65
184
183
21,02
23,00
27,0
32,3
563
610
4,73
4,65
186
183
26,94
29,21
40,4
33,2
650
690
748
4,67
4,75
4,71
184
187
186
31,11
33,00
35,81
37,6
42,3
35,6
N°
2
2
2
2
2
2
2
2
2
N°
2
2
2
2
2
2
2
2
2
kg
65,0
76,0
86,0
dB(A)
56
57
57
dB(A)
88
89
89
mm
4000
5250
5250
mm
2260
2260
2260
mm
2640
2640
2640
94,0
57
89
5250
2260
2640
109
57
90
6500
2260
2640
117
58
91
6500
2260
2640
126
134
143
58
59
59
91
92
92
7750
7750
7750
2260
2260
2260
2640
2640
2640
4720
V/ph/Hz
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
kg
3930
4540
4660
6200
1046
1118
309,2
329,8
3,383
3,390
4,640
4,670
1046
1117
3,340
3,350
4,460
4,480
6500
6960
7100
7190
0852
0902
1322
1402
1002
905,0
987,3
265,5
287,7
3,409
3,432
4,630
4,680
904,3
986,6
3,370
3,380
4,460
4,470
1052
1152
1222
1191
350,7
3,396
4,660
1190
3,350
4,460
kW
834,3
kW
245,3
kW/kW
3,401
kW/kW
4,620
kW
833,7
kW/kW
3,370
kW/kW
4,470
1295
390,7
3,315
4,590
1294
3,280
4,460
1355
408,0
3,321
4,620
1354
3,290
4,460
-
-
-
-
-
-
-
-
kW
834
4,71
%
186
l/s
39,90
904
987
1046
4,74
4,79
4,72
187
189
186
43,28
47,22
50,04
1117
1190
1294
1354
4,74
4,74
4,65
4,69
187
187
183
185
53,45
56,95
61,94
64,80
51,8
57,6
38,8
42,4
kPa
39,0
45,9
59,5
47,4
N
°
2
2
2
2
2
2
2
2
N
°
2
2
2
2
2
2
2
2
kg
160
173
dB(A)
59
59
dB(A)
92
92
mm
9000
9000
mm
2260
2260
mm
2640
2640
kg
8120
8690
188
200
213
227
244
258
59
60
60
60
60
62
92
93
93
93
93
95
1 4 Acqua scambiatore freddo lato utenza (in/out) 12°C/7°C; Aria scambiatore lato sorgente (in) 35°C.
2 4 Valori riferiti alla normativa EN14511
3 4 Livello di pressione sonora medio a 10m di distanza, per unità in campo libero su superficie riflettente;
valore non vincolante calcolato dalla potenza sonora.
4 4 Potenza sonora sulla base di misure effettuate in accordo alla normativa ISO 9614.
Le unità, evidenziate nella presente pubblicazione, contengono gas fluorurato R513A [GWP
100
631] ad effetto serra.
5 4 Potenza sonora in refrigerazione, outdoors.
6 4 Unità in configurazione ed esecuzione standard, priva di accessori opzionali.
7 4 Parametro calcolato in accordo con il [REGOLAMENTO (UE) N. 2016/2281].
8 4 Indice di efficienza energetica stagionale.
9 4 Efficienza energetica stagionale del raffreddamento d’ambiente.
10250
10250
11650
2260
2260
2260
2640
2640
2640
9210
9560
10080
11650
11650
12900
2260
2260
2260
2640
2640
2640
10200
11140
11810
Dati certificati in EUROVENT