PREMANT district heating pipe

District heating pipe – UNO

PRE 6.300

Heating

200

D = outer diameter of casing pipe

d = outer diameter of medium pipe

PREMANT

Nominal

Steel pipe

width

d x s

DN

mm

20

26.9 x 2.6

25

33.7 x 2.6

32

42.4 x 2.6

40

48.3 x 2.6

50

60.3 x 2.9

65

76.1 x 2.9

80

88.9 x 3.2

100

114.3 x 3.6

125

139.7 x 3.6

150

168.3 x 4.0

200

219.1 x 4.5

250

273.0 x 5.0

300

323.9 x 5.6

350

355.6 x 5.6

400

406.4 x 6.3

450

457.2 x 6.3

500

508.0 x 6.3

600

610.0 x 7.1

700

711.0 x 8.0

800

813.0 x 8.8

900

914.0 x 10.0

1000

1016.0 x 11.0

L

s = wall thickness of medium pipe

t = insulation thickness

Insulation thickness 1

D

Insulation thickness 2

D

Insulation thickness 3

D

Figures in mm

Delivery

Volume

length

Inner pipe

m

l/m

6

0.37

6

0.67

6/12

1.09

6/12

1.46

6/12

2.33

6/12

3.88

6/12

5.35

6/12/16

9.01

6/12/16

13.79

6/12/16

20.18

6/12/16

34.67

6/12/16

54.33

6/12/16

76.80

6/12/16

93.16

6/12/16

121.80

6/12/16

155.25

6/12/16

192.75

6/12/16

278.80

6/12/16

379.37

6/12/16

496.98

6/12

627.72

6

776.00

mm

90

90

110

110

125

140

160

200

225

250

315

400

450

500

560

630

710

800

900

1000

1100

1200

kg/m

2.7

3.1

4.0

4.4

5.8

7.1

9.0

13.0

15.9

20.5

30.5

43.5

56.2

63.7

81.0

93.5

108

140

180

223

279

337

mm

110

110

125

125

140

160

180

225

250

280

355

450

500

560

630

710

800

900

1000

1100

1200

-

kg/m

3.1

3.5

4.3

4.7

6.1

7.6

9.6

13.9

16.9

22.3

32.5

47.0

60.5

69.3

88.0

103

118

154

196

240

298

-

mm

125

125

140

140

160

180

200

250

280

315

400

500

560

630

710

800

900

1000

1100

1200

-

-

kg/m

3.4

3.8

4.7

5.0

6.6

8.2

10.3

15.0

18.7

24.0

35.8

51.3

66.1

76.3

97.7

113

133

170

213

259

-

-

23.5.2023 BGP

Subject to technical changes

t

s

d

D