General
We only provide systematic heat insulation for ball valves if they are
suitable for direct installation in the ground, with or without pre-
stressing, i.e.:
A. if they fulfil the requirements acc. EN 488
B. if there are no screwed connectors in the insulated area.
Range of applications
• Upto160°C/16baror140°C/25bar
• Processed, deminer alized, clean tap water with low oxygen content
• not suitable for installation in the area of bends and expansion limbs
Material
• Housing made of steel, forged and welded.
• Ball in stainless steel
• Switching spindle in stainless steel
• Seals in reinforced Teflon
• Ball seal, spring-supported
• Spindle seal, multiple
• Monitoring wire, foamed in
• Heat insulation made of rigid PUR foam
• HDPE casing
Delivery and storage
• Ball valves in open position
• Protective caps on both pipe ends
Assembly / installation
• Only weld in the ball valves in the open position, and protect the
housing against overheating while doing so
• Install expansion pads in the area of the dome, as per the instructions
• Pay special attention to ensure that the dome has sufficient freedom
of movement
• The upper uninsulated section of the spindle must not stand in the
groundwater/other water
• The first switching operation must only take place after the pipe has
been flushed through (open the gate valve first)
• Ifthereisariskoffrost,uncoveredfittingsmustbecompletelyemptied
• Thoroughly grease the steel parts on the dome
• Ifthereisaprovisionalpipeend,thefreepipeendmustbeweldedshut
Position indicator
• Milled-in notch on switch spindle square, and pointer
Activation
• Close by turning to the right (clockwise) as far as the stop
(90° for ball valve)
Operation
• Matching socket wrenches must be used for switching
• Plug-on gears with matching receiver components can be supplied
for ball valves (our recommendation for DN 200 and above)
• Do not apply force to the switching shaft
• Do not overtighten the end stops
• Intermediate positions are not allowed for ball valves due to the
possbility of wear on the ball seals
• The processed tapwater must not contain any solid particles
because they could damage the sealing surfaces
Maintenance
• Periodically clean the steel parts on the dome and grease them
thoroughly
• Switch between OPEN and CLOSED several times, at least every
3 months, until smooth running is achieved
• Check the freedom of movement of the dome
• Check the groundwater level and condition
Important
It is essential to follow the above instructions. We and/or the
fittings manufacturer cannot provide any warranty for damage due
to incorrect installation, handling and maintenance.
23.5.2023 BGP
Subject to technical changes