HP
4 HP
5 HP
6 HP
4 HP
5 HP
6 HP
V
220-230-240
220-230-240
220-230-240
380-400-415
380-400-415
380-400-415
Monofase
Monofase
Monofase
Monofase
Monofase
Monofase
H
z
5
0
5
0
5
0
5
0
5
0
50
A
1,00
1,00
1,00
1,00
1,00
1,00
A
17,30
24,30
27,40
7,90
10,10
10,70
Unità esterne
U-4LE2E5
U-5LE2E5
U-6LE2E5
U-4LE2E8
U-5LE2E8
U-6LE2E8
Alimentazione
Fase
Frequenza
Voltaggio
Capacità raffrescam.
kW
12,1
14,0
15,5
12,1
14,0
15,5
Coefficiente EER
1)
W/W
4,50
4,06
3,73
4,50
4,06
3,73
Assorbimento
A
13,30 - 12,70 - 12,20
16,30 - 15,60 - 17,00
20,30 - 19,40 - 18,60
4,39 - 4,17 - 4,02
5,58 - 5,30 - 5,11
6,71 - 6,37 - 6,14
Consumo in raffresc.
kW
2,69
3,45
4,15
2,69
3,45
4,15
Capacità in riscald.
kW
12,5
16,0
16,5
12,5
16,0
16,5
Coefficiente COP
1)
W/W
5,19
4,60
4,27
5,19
4,60
4,27
Assorbimento
A
12,20 - 11,60 - 11,20
17,60 - 16,80 - 16,10
19,10 - 18,20 - 17,50
3,98 - 3,78 - 3,64
5,62 - 5,34 - 5,14
6,24 - 5,93 - 5,71
Consumo in riscald.
kW
2,41
3,48
3,86
2,41
3,48
3,86
Corrente di spunto
Assorbimento max
Consumo massimo
kW
3,50-3,66-3,82
4,92-5,14-5,37
5,61-5,86-6,12
4,34-5,09-5,28
6,25-6,55-6,82
6,62-6,97-7,23
Numero massimo di unit
à interne collegabili
2)
7 (10)
0~35
69
52
8 (10)
0~35
72
53
9 (12)
0~35
74
54
7 (10)
0~35
69
52
8 (10)
0~35
72
53
9 (12)
0~35
74
53
Pressione statica esterna
Pa
m3/min
dB(A)
Portata d'aria
Livello pressione
sonora
Liv. potenza sonora
Dimensioni
Peso netto
Tubi di collegamento
Lunghezza massima tubazioni (totale)
Differenza in elevazione (int/est)
Refrigerante (R410A) / CO
2
Eq.
Rapporto di capacità unità interna / esterna
(min / max)
3)
Gamma temp.
Raffresc. Min ~ Max
esterne operative
Riscald. Min ~ Max
Raffrescamento
Raffr.(Sil.1/2/3/4)
Riscaldamento
Raffr. / Riscaldam.
AxLxP
Lato liquido
Lato gas
dB(A)
50,5/49/47/45
51,5/50/48/46
52,5/51/48/46
50,5/49/49/47
48,5/50/48/46
48,5/50/48/46
dB(A)
dB(A)
mm
kg
Poll. (mm)
Poll. (mm)
m
m
kg / T
%
°C
°C
54
69/72
996x980x370
106
3/8 (9,52)
5/8 (15,88)
150 (180)
50 (U.E. in posiz.
superiore) /
40 (U.E. in posiz.
inferiore)
6,70 (14,40) /
13,9896
50~130
-10~+46
-20 ~ +18
56
71/75
996x980x370
106
3/8 (9,52)
5/8 (15,88)
150 (180)
50 (U.E. in posiz.
superiore) /
40 (U.E. in posiz.
inferiore)
6,70 (14,40) /
13,9896
50~130
-10~+46
-20 ~ +18
56
73/75
996x980x370
106
3/8 (9,52)
5/8 (15,88)
150 (180)
50 (U.E. in posiz.
superiore) /
40 (U.E. in posiz.
inferiore)
6,70 (14,40) /
13,9896
50~130
-10~+46
-20 ~ +18
54
69/72
996x980x370
106
3/8 (9,52)
5/8 (15,88)
150 (180)
50 (U.E. in posiz.
superiore) /
40 (U.E. in posiz.
inferiore)
6,70 (14,40) /
13,9896
50~130
-10~+46
-20 ~ +18
56
71/75
996x980x370
106
3/8 (9,52)
5/8 (15,88)
150 (180)
50 (U.E. in posiz.
superiore) /
40 (U.E. in posiz.
inferiore)
6,70 (14,40) /
13,9896
50~130
-10~+46
-20 ~ +18
56
73/75
996x980x370
106
3/8 (9,52)
5/8 (15,88)
150 (180)
50 (U.E. in posiz.
superiore) /
40 (U.E. in posiz.
inferiore)
6,70 (14,40) /
13,9896
50~130
-10~+46
-20 ~ +18
ErP data
3)
SEER
4)
7,85
7,48
7,25
7,85
7,48
7,25
η
s,c
311,0%
296,2%
286,8%
311,0%
296,2%
286,8%
SCOP
4)
4,87
4,40
4,24
4,87
4,40
4,24
η
s,h
191,8%
172,9%
166,7%
191,8%
172,9%
166,7%
1) EER e COP calcolati in base alla direttiva EN14511. 2) In caso di collegamento di unit
à interne da 1,5 kW, è possibile collegare al massimo 12 unità interne. 3) SEER / SCOP e ηs,c / ηs,h sono conformi ai dati
dei test ErP per le unità interne a scomparsa a pressione statica variabile di tipo F2. Certificato Eurovent. 4) SEER / SCOP
è calcolato in base ai valori di efficienza stagionale di raffrescamento/riscaldamento
degli ambienti "η" del REGOLAMENTO (UE) 2016/2281 DELLA COMMISSIONE. SEER, SCOP = (η + Correzione) × PEF.
COMPRESSORE
R2 ROTARY
BLUEFIN
-10 °C
MODALITÀ
RAFFRESCAMENTO
-20 °C
MODALITÀ
RISCALDAMENTO
RIAVVIO
AUTOMATICO
R22
R410A
R22 RENEWAL
PANASONIC
AC SMART CLOUD
WI-FI OPZIONALE
ANNI
DI GARANZIA SUL
106
INTERNET CONTROL: opzionale.
COMPRESSORE