HP
Alimentazione
Corr. di spunto
18 HP
V
380-400-415
Trifase
20 HP
380-400-415
Trifase
22 HP
24 HP
26 HP
28 HP
30 HP
32 HP
Unità esterne
U-8MF3E8
U-8MF3E8
U-10MF3E8
U-12MF3E8
U-10MF3E8
U-12MF3E8
U-14MF3E8
U-16MF3E8
U-10MF3E8
U-12MF3E8
U-12MF3E8
U-12MF3E8
U-16MF3E8
U-16MF3E8
U-16MF3E8
U-16MF3E8
Voltaggio
Fase
Frequenza
380-400-415
Trifase
380-400-415
Trifase
380-400-415
Trifase
380-400-415
Trifase
380-400-415
Trifase
380-400-415
Trifase
Hz
50
50
50
50
50
50
50
50
Capacità in raffr.
kW
50,0
56,0
61,5
68,0
73,0
78,5
85,0
90,0
Coefficiente EER
1)
W/W
4,90
4,31
4,24
3,89
3,88
3,65
3,59
3,49
Assorbimento
A
16,80-16,00-15,40
21,00-20,00-19,20
23,70-22,50-21,70
28,30-26,90-25,90
31,00-29,50-28,40
35,10-33,40-32,20
39,60-37,60-36,20
42,60-40,50-39,00
Cons. in raffresc.
kW
10,20
13,00
14,50
17,50
18,80
21,50
23,70
25,8
Cap. in riscald.
kW
56,0
63,0
69,0
76,5
81,5
87,5
95,0
100,0
Coefficiente COP
1)
W/W
5,23
4,77
4,79
4,47
4,50
4,31
4,19
4,17
Assorbimento
A
17,70-16,80-16,20
21,30-20,30-19,50
23,50-22,30-21,50
27,60-26,30-25,30
30,20-28,70-27,70
33,50-31,80-30,70
37,90-36,00-34,70
40,10-38,10-36,70
Cons. in riscald.
kW
10,70
13,20
14,40
17,10
18,10
20,30
22,70
24,00
Pressione statica esterna (Max)
A
2,00
Pa
80
m3/min
430
dB(A)
59,0
2,00
80
442
61,0
58,0 / 56,0
84,0
1842 x 2360
(+60) x 1000
547
5/8 (15,88) /
3/4 (19,05)
7/8 (22,22) /
1 (25,40)
1-1/8 (28,58) /
1-1/4 (31,75)
1/4 (6,35)
15,10 / 31,5288
50~150
-10 ~ +52
-20 ~ +18
-10 ~ +24
36 HP
380-400-415
Trifase
2,00
80
452
62,0
59,0 / 57,0
84,5
1842 x 2360
(+60) x 1000
548
5/8 (15,88) /
3/4 (19,05)
1 (25,40) /
1-1/8 (28,58)
1-1/8 (28,58) /
1-1/4 (31,75)
1/4 (6,35)
15,10 / 31,5288
50~150
-10 ~ +52
-20 ~ +18
-10 ~ +24
38 HP
380-400-415
Trifase
2,00
80
464
63,0
60,0 / 58,0
86,0
1842 x 2360
(+60) x 1000
574
5/8 (15,88) /
3/4 (19,05)
1 (25,40) /
1-1/8 (28,58)
1-1/8 (28,58) /
1-1/4 (31,75)
1/4 (6,35)
16,60 / 34,6608
50~150
-10 ~ +52
-20 ~ +18
-10 ~ +24
40 HP
380-400-415
Trifase
3,00
80
452
63,5
60,5 / 58,5
84,5
1842 x 2360
(+60) x 1000
596
3/4 (19,05) /
7/8 (22,22)
1 (25,40) /
1-1/8 (28,58)
1-1/4 (31,75) /
1-1/2 (38,10)
1/4 (6,35)
15,10 / 31,5288
50~150
-10 ~ +52
-20 ~ +18
-10 ~ +24
42 HP
380-400-415
Trifase
3,00
80
464
64,5
61,5 / 59,5
86,0
1842 x 2360
(+60) x 1000
620
3/4 (19,05) /
7/8 (22,22)
1-1/8 (28,58) /
1-1/4 (31,75)
1-1/4 (31,75) /
1-1/2 (38,10)
1/4 (6,35)
16,60 / 34,6608
50~150
-10 ~ +52
-20 ~ +18
-10 ~ +24
44 HP
380-400-415
Trifase
4,00
80
464
64,5
61,5 / 59,5
86,0
1842 x 2360
(+60) x 1000
668
3/4 (19,05) /
7/8 (22,22)
1-1/8 (28,58) /
1-1/4 (31,75)
1-1/4 (31,75) /
1-1/2 (38,10)
1/4 (6,35)
16,60 / 34,6608
50~150
-10 ~ +52
-20 ~ +18
-10 ~ +24
46 HP
380-400-415
Trifase
4,00
80
464
65,0
62,0 / 60,0
86,0
1842 x 2360
(+60) x 1000
668
3/4 (19,05) /
7/8 (22,22)
1-1/8 (28,58) /
1-1/4 (31,75)
1-1/4 (31,75) /
1-1/2 (38,10)
1/4 (6,35)
16,60 / 34,6608
50~150
-10 ~ +52
-20 ~ +18
-10 ~ +24
48 HP
380-400-415
Trifase
Portata d'aria
Livello pressione
sonora
Liv. pot. sonora
Dimensioni
Peso netto
Tubi di
collegamento
2)
Mod. Normale
Mod. Silenz. 1 / 2 dB(A)
56,0 / 54,0
Refrigerante (R410A) / CO
2
Eq.
Rapporto di capacità unità int. / est. (min
mm
kg
Poll. (mm)
Poll. (mm)
Poll. (mm)
Poll. (mm)
kg / T
/ max)
°C
°C
°C
V
Hz
A
Pa
m3/min
dB(A)
dB(A)
dB(A)
mm
kg
Poll. (mm)
Poll. (mm)
Poll. (mm)
Poll. (mm)
kg / T
/ max)
°C
°C
°C
1842 x 2360
(+60) x 1000
523
5/8 (15,88) /
3/4 (19,05)
7/8 (22,22) /
1 (25,40)
1-1/8 (28,58) /
1-1/4 (31,75)
1/4 (6,35)
13,60 / 28,3968
50~150
-10 ~ +52
-20 ~ +18
-10 ~ +24
34 HP
380-400-415
Trifase
Mod. Normale
AxLxP
Lato liquido
Scarico
Aspirazione
Bilanciamento
dB(A)
81,5
Gamma temp.
esterne operative
HP
Alimentazione
Corr. di spunto
Raffr. Min ~ Max
Risc. Min ~ Max
Op. simultanea
Voltaggio
Fase
Frequenza
50
50
50
50
50
50
50
50
Unità esterne
U-8MF3E8
U-8MF3E8
U-10MF3E8
U-8MF3E8
U-10MF3E8
U-12MF3E8
U-14MF3E8
U-16MF3E8
U-10MF3E8
U-12MF3E8
U-12MF3E8
U-16MF3E8
U-16MF3E8
U-16MF3E8
U-16MF3E8
U-16MF3E8
U-16MF3E8
U-16MF3E8
U-16MF3E8
U-16MF3E8
U-16MF3E8
U-16MF3E8
U-16MF3E8
U-16MF3E8
Capacità in raffr.
kW
96,0
101,0
107,0
113,0
118,0
124,0
130,0
135,0
Coefficiente EER
1)
W/W
4,10
3,90
3,88
3,72
3,72
3,58
3,55
3,49
Assorbimento
A
38,60-36,70-35,40
42,30-40,20-38,70
45,60-43,30-41,70
50,20-47,70-46,00
52,40-49,70-47,90
56,50-53,70-51,80
61,10-58,10-56,00
63,90-60,70-58,50
Cons. in raffresc.
kW
23,40
25,90
27,60
30,40
31,70
34,60
36,60
38,70
Cap. in riscald.
kW
108,0
113,0
119,0
127,0
132,0
138,0
145,0
150,0
Coefficiente COP
1)
W/W
4,64
4,48
4,51
4,31
4,36
4,25
4,18
4,17
Assorbimento
A
38,90-37,00-35,60
41,60-39,50-38,10
43,60-41,40-39,90
49,30-46,80-45,10
50,60-48,10-46,30
53,70-51,00-49,10
57,90-55,00-53,00
60,10-57,10-55,00
Cons. in riscald.
kW
23,30
25,20
26,40
29,50
30,30
32,50
34,70
36,00
Pressione statica esterna (Max)
4,00
80
662
64,0
61,0 / 59,0
84,5
1842 x 3540
(+120) x 1000
857
3/4 (19,05) /
7/8 (22,22)
1-1/8 (28,58) /
1-1/4 (31,75)
1-1/4 (31,75) /
1-1/2 (38,10)
1/4 (6,35)
21,90/45,72719
50~150
-10~+52
-20~+18
-10~+24
4,00
80
674
64,5
61,5 / 59,5
85,5
1842 x 3540
(+120) x 1000
881
3/4 (19,05) /
7/8 (22,22)
1-1/8 (28,58) /
1-1/4 (31,75)
1-1/2 (38,10) /
1-5/8 (41,28)
1/4 (6,35)
23,40/48,85919
50~150
-10~+52
-20~+18
-10~+24
4,00
80
684
65,0
62,0 / 60,0
85,5
1842 x 3540
(+120) x 1000
882
3/4 (19,05) /
7/8 (22,22)
1-1/4 (31,75) /
1-1/2 (38,10)
1-1/2 (38,10) /
1-5/8 (41,28)
1/4 (6,35)
23,40/48,85919
50~150
-10~+52
-20~+18
-10~+24
5,00
80
674
65,5
62,5 / 60,5
85,5
1842 x 3540
(+120) x 1000
929
3/4 (19,05) /
7/8 (22,22)
1-1/4 (31,75) /
1-1/2 (38,10)
1-1/2 (38,10) /
1-5/8 (41,28)
1/4 (6,35)
23,40/48,85919
50~150
-10~+52
-20~+18
-10~+24
5,00
80
684
66,0
63,0 / 61,0
86,0
1842 x 3540
(+120) x 1000
930
3/4 (19,05) /
7/8 (22,22)
1-1/4 (31,75) /
1-1/2 (38,10)
1-1/2 (38,10) /
1-5/8 (41,28)
1/4 (6,35)
23,40/48,85919
50~150
-10~+52
-20~+18
-10~+24
5,00
80
696
66,5
63,5 / 61,5
86,5
1842 x 3540
(+120) x 1000
954
3/4 (19,05) /
7/8 (22,22)
1-1/4 (31,75) /
1-1/2 (38,10)
1-1/2 (38,10) /
1-5/8 (41,28)
1/4 (6,35)
24,90 / 46,3536
50~150
-10~+52
-20~+18
-10~+24
6,00
80
696
66,5
63,5 / 61,5
87,0
1842 x 3540
(+120) x 1000
1002
3/4 (19,05) /
7/8 (22,22)
1-1/4 (31,75) /
1-1/2 (38,10)
1-1/2 (38,10) /
1-5/8 (41,28)
1/4 (6,35)
24,90 / 51,9912
50~150
-10~+52
-20~+18
-10~+24
6,00
80
696
67,0
64,0 / 62,0
87,0
1842 x 3540
(+120) x 1000
1002
3/4 (19,05) /
7/8 (22,22)
1-1/4 (31,75) /
1-1/2 (38,10)
1-1/2 (38,10) /
1-5/8 (41,28)
1/4 (6,35)
24,90 / 51,9912
50~150
-10~+52
-20~+18
-10~+24
Portata d'aria
Livello pressione
sonora
Liv. pot. sonora
Dimensioni
Peso netto
Tubi di
collegamento
2)
Mod. Normale
Mod. Silenz. 1 / 2
Mod. Normale
AxLxP
Lato liquido
Scarico
Aspirazione
Bilanciamento
Refrigerante (R410A) / CO
2
Eq.
Rapporto di capacità unità int. / est. (min
Gamma temp.
Raffr. Min ~ Max
esterne operative
Risc. Min ~ Max
Op. simultanea
1) EER e COP calcolati in base alla normativa EN14511. 2) Diametro delle tubazioni inferiore a 90 m
più lunga supera i 90 m, aumentare le dimensioni dei tubi principali di 1 grado per i tubi del gas e
per l'unità interna finale / superiore a 90 m per l'unità interna finale (se la lunghezza equivalente della tubazione
i tubi del liquido).
Condizioni di operatività: Raffrescamento interno 27 °C DB / 19 °C WB. Raffrescamento esterno 35 °C DB / 24 °C WB. Riscaldamento interno 20 °C DB. Riscaldamento esterno 7 °C DB / 6 °C WB. (DB: Bulbo secco; WB: Bulbo umido). Specifiche soggette a
modifiche senza preavviso. Per informazioni dettagliate su ErP / Etichettatura energetica, visitare i nostri siti web www.aircon.panasonic.eu o www.ptc.panasonic.eu.
129