UNITÀ INTERNE IDRONICHE

Canalizzata a bassa prevalenza (EC)

Potenza assorbb. 2-tubi

Potenza assorbb. 4-tubi

Collegamenti idraulici

Tipo

2-tubi

4-tubi

Dimensioni e peso

Dimensioni

Peso

Comando a filo opzionale

avanzato con touch

control.

PAW-FC-907EC

Comando opzionale a filo.

PAW-FC-903EC

2-tubi - connessione lato sx (PAW-)

Sigla

FC2E-D010L

FC2E-D020L

FC2E-D030L

FC2E-D040L

FC2E-D050L

FC2E-D060L

FC2E-D070L

FC2E-D080L

FC2E-F040L

2-tubi - connessione lato dx (PAW-)

Sigla

FC2E-D010R

FC2E-D020R

FC2E-D030R

FC2E-D040R

FC2E-D050R

FC2E-D060R

FC2E-D070R

FC2E-D080R

FC2E-F040R

Capacità sensibile

1)

Lo/Med/Hi

kW

0,5/1,1/1,9

0,5/1,1/1,9

0,6/1,6/2,4

1,0/2,1/3,0

1,1/3,0/3,7

1,4/3,5/4,0

2,0/4,3/5,2

3,7/4,8/6,6

2,9/6,1/9,1

Portata d’acqua

Lo/Med/Hi

l/h

107/210/356

110/237/406

148/354/532

230/506/722

231/685/743

341/767/800

463/1008/1098

879/1111/1254

627/1142/1575

Perdita di carico acqua

Lo/Med/Hi

kPa

8,2 / 28,2 / 76,9

1,5/4,6/11,0

5,0 / 20,5 / 42,1

6,4 / 24,4 / 46,3

4,9 / 35,1 / 41,0

7,8 / 35,8 / 38,8

3,0 / 14,0 / 16,6

14,1/21,4/26,6

10,6/51,2/93,8

Capacità riscaldamento

2)

Lo/Med/Hi

kW

0,8/1,6/2,9

0,9/1,9/3,3

1,0/2,2/3,4

1,4/3,0/5,3

1,7/5,2/5,5

2,3/5,9/6,1

3,8/7,3/8,2

6,2/8,0/9,3

4,4/8,3/11,8

4-tubi - connessione lato sx (PAW-)

Sigla

FC4E-D010L

FC4E-D020L

FC4E-D030L

FC4E-D040L

FC4E-D050L

FC4E-D060L

FC4E-D070L

FC4E-D080L

FC4E-F040L

4-tubi - connessione lato dx (PAW-)

Sigla

FC4E-D010R

FC4E-D020R

FC4E-D030R

FC4E-D040R

FC4E-D050R

FC4E-D060R

FC4E-D070R

FC4E-D080R

FC4E-F040R

Capacità raffrescamento

1)

Lo/Med/Hi

kW

0,6/1,2/2,1

0,6/1,4/2,4

0,9/2,1/3,1

1,3/2,9/4,2

1,3/4,0/5,0

2,0/4,5/5,2

2,7/5,9/6,9

5,1/6,5/8,8

3,6/6,6/9,2

Capacità tot. raffresc.

1)

Lo/Med/Hi

kW

0,5/1,1/1,9

0,6/1,2/2,2

0,8/1,9/2,9

1,2/2,7/4,0

1,2/3,6/4,6

1,8/4,1/4,9

2,6/5,1/6,4

5,0/6,2/9,6

3,3/6,4/8,8

Capacità sensibile

1)

Lo/Med/Hi

kW

0,4/0,9/1,7

0,4/1,0/1,8

0,6/1,5/2,2

0,9/1,9/2,8

1,0/2,8/3,5

1,2/3,2/3,8

1,9/3,8/4,8

3,6/4,6/7,2

2,7/5,6/8,0

Portata d’acqua

Lo/Med/Hi

l/h

92/185/327

97/206/375

129/321/493

205/457/681

212/625/686

306/707/749

443/886/977

855/1070/1242

567/1093/1511

Perdita di carico acqua

Lo/Med/Hi

kPa

5,8 / 20,1 / 59,2

1,3/3,7/9,7

4,0/9,2/19,7

6,3 / 29,6 / 60,1

2,5 / 17,9 / 21,3

5,1 / 24,3 / 27,2

3,5 / 13,6 / 16,5

22,9/33,9/44,3

10,0/47,2/86,7

Capacità riscaldam.

2)

Lo/Med/Hi

kW

0,4/0,8/1,4

0,6/0,9/1,5

1,0/1,4/1,8

1,2/2,0/2,8

1,6/2,4/2,5

1,4/2,9/3,1

2,5/3,4/3,6

4,5/5,9/6,9

2,5/4,5/6,2

Portata d’acqua

Lo/Med/Hi

l/h

76/140/235

95/161/255

166/243/304

204/350/483

267/416/438

233/503/531

434/583/614

767/1011/1194

432/783/1065

Perdita di carico acqua

Lo/Med/Hi

kPa

1,8/4,0/8,4

1,4/3,8/9,4

5,3/9,7/14,1

15,6/41,8/76,3

11,9/26,3/28,9

11,5/43,6/48,1

61,5/103,8/113,9

42,1/69,7/95,1

30,6/107,6/214,8

Livelli sonori

Potenza sonora globale Lo/Med/Hi

Press. sonora globale

4)

Lo/Med/Hi

Ventola

Numero

1

1

1

2

2

2

2

3

1

dB(A)

34/47/60

34/47/60

31/50/59

29/44/52

30/51/57

32/54/58

40/54/59

51/56/64

42/58/68

3)

dB(A)

25/38/51

25/38/51

22/41/50

20/35/43

21/42/48

23/45/49

31/45/50

42/47/55

23/39/52

Flusso aria 2-tubi

Flusso aria 4-tubi

Pressione esterna

Filtro

Dati elettrici

Lo/Med/Hi

Lo/Med/Hi

Max

m3/h 108 / 228 / 417 98 / 234 / 413 145 / 380 / 585 170 / 412 / 678 203 / 645 / 816 245 / 737 / 912 350/850/1050 685/927/1398 592/1284/1935

m3/h 91/199/379 84/200/380 123/342/540 148/369/627 185/587/646 205/668/716 329/798/894 660/884/1079 523/1222/1864

P

a

7

5

7

5

7

5

10

5

7

0

10

5

11

5

7

0

190

G2

G2

G2

G2

G2

G2

G2

G2

G2

Voltaggio

Alimentazione

Fase

V

Hz

Poll.

1/2

1/2

1/2

1/2

1/2

1/2

3/4

3/4

3/4

Poll.

1/2

1/2

1/2

1/2

1/2

1/2

3/4

3/4

3/4

Poll.

1/2

1/2

1/2

1/2

1/2

1/2

1/2

1/2

1/2

mm 220 x 570 x 430 220 x 570 x 430 220 x 730 x 430 220 x 938 x 430 220x1122x430 220x1307x430 220x1121x530 220x1316x530 223x1233x653

kg

13/14

13/14

15/16

20/22

22/24

26/28

27/29

38/40

19/19

230

Monofase

230

Monofase

230

Monofase

230

Monofase

230

Monofase

230

Monofase

230

Monofase

230

Monofase

230

Monofase

Frequenza

Lo/Med/Hi

Lo/Med/Hi

Raffresc.

Riscald.

AxLxP

2 / 4-tubi

50/60

W

5/11/41

5/13/41

4/16/42

2/13/43

4/24/46

2/30/54

11/44/77

23/42/108

11/62/197

W

5/11/39

5/13/40

6/15/40

2/12/42

2/23/44

2/28/52

11/43/75

22/41/116

11/60/188

Filettato gas Filettato gas Filettato gas Filettato gas Filettato gas Filettato gas Filettato gas Filettato gas Filettato gas

femmina

femmina

femmina

femmina

femmina

femmina

femmina

femmina

femmina

50/60

50/60

50/60

50/60

50/60

50/60

50/60

50/60

1) Secondo lo standard Eurovent. Aria: 27 °C DB / 19 °C WB. Acqua in ingresso / in uscita: 7 °C / 12 °C. 2) Aria: 20 °C. Acqua in ingresso / in uscita: 45 °C / 40 °C. 3) I livelli di potenza sonora indicati si riferiscono a

misure di ritorno e di irradiazione. 4) livelli di pressione sonora si basano sulle caratteristiche (NR) di una stanza con volume di 100 m3) con riverbero di 0,5 secondi. I valori indicati sono per pressione statica esterna

0 Pa, per caratteristiche di pressione aggiuntive, consultare il manuale dei dati tecnici.

Particolarità tecniche

· · Capacità di raffrescamento da 0,5 a 9,6 kW

· Capacità di riscaldamento da 0,6 a 13,6 kW

· Ventola (e) EC a basso consumo energetico

Limiti di operatività

Temperatura acqua in ingresso

Temperatura interna

ErP

VENTILAZIONEVERDE

MOTORE EC

Da 5 a 90 °C

Da 5 a 32 °C

Principali caratteristiche e accessori

· Configurazione a 2 e 4-tubi

· Connessioni dal lato destro e sinistro

· Possibilità di installazione orizzontale e verticale*

· Facilità di installazione

· Livelli di rumorosità molto bassi

· Valvole ON/OFF a 2 o a 3 vie

· Vaschetta di drenaggio ausiliaria

· Presa d’aria con griglia rimovibile

· Filtro G2

* PAW-FC2E-F040 e PAW-FC4E-F040 possono essere installati solo in orizzontale.

ERP 2018: conforme al REGOLAMENTO DELLA COMMISSIONE (UE) n. 2016/2281.

301