PAW heating systems - Dimensioning tables

CoolBloC series

Max. output / Application range CoolBloC series

C31

DN 20 (3⁄4")

Page

DN 25 (1")

Page

DN 32 (11⁄4")

Page

DN 40 (11⁄2")

Page

DN 50 (2") Page

∆ t = 20 K

46,5 kW

142

50 kW

144

∆ t = 10 K

23 kW

142

25 kW

144

∆ t = 7.5 K

17 kW

142

19 kW

144

∆ t =5 K

11,5 kW

142

12,5 kW

144

C34

DN 20 (3⁄4")

Page

DN 25 (1")

Page

DN 32 (11⁄4")

Page

DN 40 (11⁄2")

Page

DN 50 (2") Page

∆ t = 20 K

43 kW

143

48 kW

145

∆ t = 10 K

21,5 kW

143

24 kW

143

∆ t = 7.5 K

16,5 kW

143

18 kW

143

∆ t =5 K

10 kW

143

12 kW

143

MV

Distribution manifold

DN 20 (3⁄4")

Page

DN 25 (1")

Page

DN 32 (11⁄4")

Page

DN 40 (11⁄2")

Page

DN 50 (2") Page

∆ t = 20 K

80 kW

150

150 kW

152

∆ t = 10 K

80 kW

150

150 kW

152

∆ t = 7.5 K

80 kW

150

150 kW

152

∆ t =5 K

80 kW

150

150 kW

152

01/2019 • Printed in Germany

PAW GmbH & Co. KG • D-31789 Hameln • Germany • Phone: +49-5151-9856-0 • Fax: +49-5151-9856-98 • info@paw.eu • www.paw.eu

11