SERIE POWER - CERTIFICAzIONI SERIE POWER
39
tr 20
tr 25
Manufacturer's Declaration for hot water boilers TR with
manual fuel supply (wood split logs)
Manufacturer
:
Products :
Type designation:
for the submission of official institutions
WVterm d.o.o.
Preradovičeva 22, 2000 Maribor, Slovenija
Hot-water boilers for wood with manual fuel supply
TR 20
The Engineering Test Institute, Public Enterprise, hereby certifies that the charactericstics of the
samples of the products concerned have been found conforming to the applicable requirements of
EN 303-5:2013.
The present Certificate has been issued on the basis of Final Report 31-9651/T of 2015-10-14,
issued by the Engineering Test Institute, Public Enterprise (SZU).
Nominal power (kW):
20
Efficiency (%):
92,7
Minimum power (kW):
10
Efficiency (%):
93
Converted values O
2
=13%
CO [mg/m3]
NOx [mg/m3]
THC [mg/ m3]
Dust [mg/ m3]
30
121
4
4
CO [mg/ m3]
NOx [mg/ m3]
THC [mg/ m3]
Dust [mg/ m3]
136
96
9
4
Converted values O
2
=13%
Hot-water boiler meets at nominal and minimum power output, the emission requirmements for Class 5.
Date
Signature
Company stamp
02.10.2015
Manufacturer's Declaration for hot water boilers TR with
manual fuel supply (wood split logs)
Manufacturer
:
Products :
Type designation:
for the submission of official institutions
WVterm d.o.o.
Preradovičeva 22, 2000 Maribor, Slovenija
Hot-water boilers for wood with manual fuel supply
TR 25
The Engineering Test Institute, Public Enterprise, hereby certifies that the charactericstics of the
samples of the products concerned have been found conforming to the applicable requirements of
EN 303-5:2013.
The present Certificate has been issued on the basis of Final Report 31-9651/T of 2015-10-14,
issued by the Engineering Test Institute, Public Enterprise (SZU).
Nominal power (kW):
25
Efficiency (%):
92,5
Minimum power (kW):
12,5
Efficiency (%):
93,5
Converted values O
2
=0%
CO [mg/ m3]
NOx [mg/ m3]
THC [mg/ m3]
Dust [mg/ m3]
31
129
4
4
CO [mg/ m3]
NOx [mg/ m3]
THC [mg/ m3]
Dust [mg/ m3]
94
147
8
3
Converted values O
2
=0%
Hot-water boiler meets at nominal and minimum power output, the emission requirmements for Class 5.
Date
Signature
Company stamp
02.10.2015
tr 30
Manufacturer's Declaration for hot water boilers TR with
manual fuel supply (wood split logs)
Manufacturer
:
Products :
Type designation:
for the submission of official institutions
WVterm d.o.o.
Preradovičeva 22, 2000 Maribor, Slovenija
Hot-water boilers for wood with manual fuel supply
TR 30
The Engineering Test Institute, Public Enterprise, hereby certifies that the charactericstics of the
samples of the products concerned have been found conforming to the applicable requirements of
EN 303-5:2013.
The present Certificate has been issued on the basis of Final Report 31-9651/T of 2015-10-14,
issued by the Engineering Test Institute, Public Enterprise (SZU).
Nominal power (kW):
30
Efficiency (%):
92,2
Minimum power (kW):
15
Efficiency (%):
94
Converted values O
2
=13%
CO [mg/ m3]
NOx [mg/ m3]
THC [mg/ m3]
Dust [mg/ m3]
32
137
4
4
CO [mg/ m3]
NOx [mg/ m3]
THC [mg/ m3]
Dust [mg/ m3]
58
199
6
2
Converted values O
2
=13%
Hot-water boiler meets at nominal and minimum power output, the emission requirmements for Class 5.
Date
Signature
Company stamp
02.10.2015