SERIE POWER - ACCESSORI
41
gt 20
gt 25
Manufacturer's Declaration for hot water boilers GT with
manual fuel supply (wood split logs)
Manufacturer
:
Products :
Type designation:
for the submission of official institutions
WVterm d.o.o.
Preradovičeva 22, 2000 Maribor, Slovenija
Hot-water boilers for wood with manual fuel supply
GT 25
The Engineering Test Institute, Public Enterprise, hereby certifies that the charactericstics of the
samples of the products concerned have been found conforming to the applicable requirements of
EN 303-5:2013.
The present Certificate has been issued on the basis of Final Report 31-9454/T of 2014-09-30,
issued by the Engineering Test Institute, Public Enterprise (SZU).
Nominal power (kW):
25
Efficiency (%):
91,5
Minimum power (kW):
12,5
Efficiency (%):
91,4
Converted values O
2
=0%
Converted values O
2
=13%
Converted values O
2
=0%
CO [mg/MJ]
NOx [mg/MJ]
THC [mg/MJ]
Dust [mg/MJ]
37
90
10
9
CO [mg/m3]
NOx [mg/m3]
THC [mg/m3]
Dust [mg/m3]
55
131
14
13,5
CO [mg/MJ]
NOx [mg/MJ]
THC [mg/MJ]
Dust [mg/MJ]
59
77
20
13
CO [mg/m3]
NOx [mg/m3]
THC [mg/m3]
Dust [mg/m3]
84
115
23,5
18
Converted values O
2
=13%
Hot-water boiler meets at nominal and minimum power output, the emission requirmements for Class 5.
Date
Signature
Company stamp
30.09.2014
Manufacturer's Declaration for hot water boilers GT with
manual fuel supply (wood split logs)
Manufacturer
:
Products :
Type designation:
for the submission of official institutions
WVterm d.o.o.
Preradovičeva 22, 2000 Maribor, Slovenija
Hot-water boilers for wood with manual fuel supply
GT 20
The Engineering Test Institute, Public Enterprise, hereby certifies that the charactericstics of the
samples of the products concerned have been found conforming to the applicable requirements of
EN 303-5:2013.
The present Certificate has been issued on the basis of Final Report 31-9454/T of 2014-09-30,
issued by the Engineering Test Institute, Public Enterprise (SZU).
Nominal power (kW):
20
Efficiency (%):
91,4
Minimum power (kW):
10
Efficiency (%):
91
Converted values O
2
=0%
Converted values O
2
=13%
Converted values O
2
=0%
CO [mg/MJ]
NOx [mg/MJ]
THC [mg/MJ]
Dust [mg/MJ]
40
88
14
10
CO [mg/m3]
NOx [mg/m3]
THC [mg/m3]
Dust [mg/m3]
60
126
20
15
CO [mg/MJ]
NOx [mg/MJ]
THC [mg/MJ]
Dust [mg/MJ]
49
78
19
10
CO [mg/m3]
NOx [mg/m3]
THC [mg/m3]
Dust [mg/m3]
71
115
29
15
Converted values O
2
=13%
Hot-water boiler meets at nominal and minimum power output, the emission requirmements for Class 5.
Date
Signature
Company stamp
30.09.2014
gt 30
Manufacturer's Declaration for hot water boilers GT with
manual fuel supply (wood split logs)
Manufacturer
:
Products :
Type designation:
for the submission of official institutions
WVterm d.o.o.
Preradovičeva 22, 2000 Maribor, Slovenija
Hot-water boilers for wood with manual fuel supply
GT 30
The Engineering Test Institute, Public Enterprise, hereby certifies that the charactericstics of the
samples of the products concerned have been found conforming to the applicable requirements of
EN 303-5:2013.
The present Certificate has been issued on the basis of Final Report 31-9454/T of 2014-09-30,
issued by the Engineering Test Institute, Public Enterprise (SZU).
Nominal power (kW):
30
Efficiency (%):
91,6
Minimum power (kW):
15
Efficiency (%):
91,7
Converted values O
2
=0%
Converted values O
2
=13%
Converted values O
2
=0%
CO [mg/MJ]
NOx [mg/MJ]
THC [mg/MJ]
Dust [mg/MJ]
33
93
5
8
CO [mg/m3]
NOx [mg/m3]
THC [mg/m3]
Dust [mg/m3]
49
136
8
12
CO [mg/MJ]
NOx [mg/MJ]
THC [mg/MJ]
Dust [mg/MJ]
68
76
21
15
CO [mg/m3]
NOx [mg/m3]
THC [mg/m3]
Dust [mg/m3]
96
114
18
21
Converted values O
2
=13%
Hot-water boiler meets at nominal and minimum power output, the emission requirmements for Class 5.
Date
Signature
Company stamp