SERIE POWER - ACCESSORI

41

gt 20

gt 25

Manufacturer's Declaration for hot water boilers GT with

manual fuel supply (wood split logs)

Manufacturer

:

Products :

Type designation:

for the submission of official institutions

WVterm d.o.o.

Preradovičeva 22, 2000 Maribor, Slovenija

Hot-water boilers for wood with manual fuel supply

GT 25

The Engineering Test Institute, Public Enterprise, hereby certifies that the charactericstics of the

samples of the products concerned have been found conforming to the applicable requirements of

EN 303-5:2013.

The present Certificate has been issued on the basis of Final Report 31-9454/T of 2014-09-30,

issued by the Engineering Test Institute, Public Enterprise (SZU).

Nominal power (kW):

25

Efficiency (%):

91,5

Minimum power (kW):

12,5

Efficiency (%):

91,4

Converted values O

2

=0%

Converted values O

2

=13%

Converted values O

2

=0%

CO [mg/MJ]

NOx [mg/MJ]

THC [mg/MJ]

Dust [mg/MJ]

37

90

10

9

CO [mg/m3]

NOx [mg/m3]

THC [mg/m3]

Dust [mg/m3]

55

131

14

13,5

CO [mg/MJ]

NOx [mg/MJ]

THC [mg/MJ]

Dust [mg/MJ]

59

77

20

13

CO [mg/m3]

NOx [mg/m3]

THC [mg/m3]

Dust [mg/m3]

84

115

23,5

18

Converted values O

2

=13%

Hot-water boiler meets at nominal and minimum power output, the emission requirmements for Class 5.

Date

Signature

Company stamp

30.09.2014

Manufacturer's Declaration for hot water boilers GT with

manual fuel supply (wood split logs)

Manufacturer

:

Products :

Type designation:

for the submission of official institutions

WVterm d.o.o.

Preradovičeva 22, 2000 Maribor, Slovenija

Hot-water boilers for wood with manual fuel supply

GT 20

The Engineering Test Institute, Public Enterprise, hereby certifies that the charactericstics of the

samples of the products concerned have been found conforming to the applicable requirements of

EN 303-5:2013.

The present Certificate has been issued on the basis of Final Report 31-9454/T of 2014-09-30,

issued by the Engineering Test Institute, Public Enterprise (SZU).

Nominal power (kW):

20

Efficiency (%):

91,4

Minimum power (kW):

10

Efficiency (%):

91

Converted values O

2

=0%

Converted values O

2

=13%

Converted values O

2

=0%

CO [mg/MJ]

NOx [mg/MJ]

THC [mg/MJ]

Dust [mg/MJ]

40

88

14

10

CO [mg/m3]

NOx [mg/m3]

THC [mg/m3]

Dust [mg/m3]

60

126

20

15

CO [mg/MJ]

NOx [mg/MJ]

THC [mg/MJ]

Dust [mg/MJ]

49

78

19

10

CO [mg/m3]

NOx [mg/m3]

THC [mg/m3]

Dust [mg/m3]

71

115

29

15

Converted values O

2

=13%

Hot-water boiler meets at nominal and minimum power output, the emission requirmements for Class 5.

Date

Signature

Company stamp

30.09.2014

gt 30

Manufacturer's Declaration for hot water boilers GT with

manual fuel supply (wood split logs)

Manufacturer

:

Products :

Type designation:

for the submission of official institutions

WVterm d.o.o.

Preradovičeva 22, 2000 Maribor, Slovenija

Hot-water boilers for wood with manual fuel supply

GT 30

The Engineering Test Institute, Public Enterprise, hereby certifies that the charactericstics of the

samples of the products concerned have been found conforming to the applicable requirements of

EN 303-5:2013.

The present Certificate has been issued on the basis of Final Report 31-9454/T of 2014-09-30,

issued by the Engineering Test Institute, Public Enterprise (SZU).

Nominal power (kW):

30

Efficiency (%):

91,6

Minimum power (kW):

15

Efficiency (%):

91,7

Converted values O

2

=0%

Converted values O

2

=13%

Converted values O

2

=0%

CO [mg/MJ]

NOx [mg/MJ]

THC [mg/MJ]

Dust [mg/MJ]

33

93

5

8

CO [mg/m3]

NOx [mg/m3]

THC [mg/m3]

Dust [mg/m3]

49

136

8

12

CO [mg/MJ]

NOx [mg/MJ]

THC [mg/MJ]

Dust [mg/MJ]

68

76

21

15

CO [mg/m3]

NOx [mg/m3]

THC [mg/m3]

Dust [mg/m3]

96

114

18

21

Converted values O

2

=13%

Hot-water boiler meets at nominal and minimum power output, the emission requirmements for Class 5.

Date

Signature

Company stamp

30.09.2014