Hydraulic separators - DN 20 (3⁄4")
Item no.
€ / piece
up to 2200 l/h
31421
-
up to 950 l/h
3142
-
Description of function
Hydraulic separators are used when there are one or more heat generation
circuits/primary circuits with pump and one or more consumer/secondary
circuits with distribution pump in one system. Due to the operating
conditions in such a system, the pumps affect each other, leading to
unwanted changes of the throughput capacity and of the head in the
circuits. The hydraulic separator causes a hydraulic separation of the
connected circuits. It is thus possible to make the connected primary and
secondary circuits work independently regarding the hydraulics. The flow in
one circuit does not cause a flow in the other circuit when the pressure drop
in the hydraulic separator is insignificant.
When a hydraulic separator is used, each circuit (the primary and the
secondary circuit) must be equipped with a pump. Thus, a heat generation
circuit/primary circuit can be provided with constant throughput and a
consumer circuit/secondary circuit can be provided with variable flow.
These are the typical functioning conditions for modern heating and air
conditioning systems.
The figures on the left side show three possible conditions of hydraulic
stability.
Completely made of brass, completely insulated with EPP insulation, for the installation under a modular
distribution manifold DN 20 or separately on the wall (vertically or horizontally).
Connections:
3⁄4" PAW flange for nut 1" (top) 3⁄4" internal thread x 1" external thread, flat-sealing (bottom), 2 x for boiler
connection, others plugged 2 × 1⁄2" int. thread for immersion sleeve and fill and drain valve Width = 435 mm
Installation height = 120 mm Centre distance = 270 mm
completely made of brass, with separate flow and return line, to be mounted under a single HeatBloC DN 20. The
EPP insulation is integrated in the HeatBloC.
Can also be installed under a distribution manifold DN 20 (with mounting plate item no. 3125) or separately in
the pipe. For separate installation, two additional union nuts item no. 2055 are required and the insulation must
be provided on site.
Connections:
3⁄4" PAW flange for nut 1" (top)
3⁄4" int. thread × 1" ext. thread, flat-sealing (bottom)
2 × 3⁄4" int. thread, sealed with plug (to the side)
Width = 260 mm
Installation height = 80 mm
Centre distance = 90 mm
Prices excl. VAT • 01/2020 • Printed in Germany
174
PAW GmbH & Co. KG • 31789 Hameln • Germany • Phone: +49-5151-9856-0 • Fax: +49-5151-9856-98 • info@paw.eu • www.paw.eu
D
N
2
0