Low-loss header MVW DN 20 (3⁄4")
for boilers with integrated pump
By means of the conversion kit (item no. 3143), the modular distribution manifolds
get a bypass which connects the flow and return line without causing any resistance
(low-loss header).
It must be considered that the pump of the boiler circuit must deliver a higher flow
rate than the consumer pumps need in total. Otherwise, unwanted circulations occur
on the right or left end of the low-loss header. In that case a hydraulic separator (item
no. 3142 or 31421) must be installed below a distribution manifold.
Please note:
When you plan the system you must already check whether
a low-loss header can be used. In combination with central
heating boilers, hydraulic separators must be installed
below / upstream of a distribution manifold as the boiler
delivers a flow rate with a high temperature difference