See page 118
See page 205
See page 118
See page 118
See page 119
566002
6 mm x 60 mm
-
3442KS1
-
See page 119
2260
-
34721
-
See page 216
See page 216
3425
-
2157
1"
-
2155
11⁄2'' internal
thread
-
34431
-
Low-loss header MVW DN 25 (1")
for boilers with integrated pump
By means of the conversion kit (item no. 34431), the modular distribution manifolds
get a bypass which connects the flow and return line without causing any resistance
(low-loss header).
It must be considered that the pump of the boiler circuit must deliver a higher flow
rate than the consumer pumps need in total. Otherwise, unwanted circulations occur
on the right or left end of the low-loss header. In that case a hydraulic separator (item
no. 344203 or 344213) must be installed below a distribution manifold.
Please note:
When you plan the system you must already check whether
a low-loss header can be used. In combination with central
heating boilers, hydraulic separators must be installed
below / upstream of a distribution manifold as the boiler
delivers a flow rate with a high temperature difference
(leads to unwanted circulation in low-loss headers).
Low-loss header MVW DN 25 (1")
Item no.
-
2-fold
Number of connections for HeatBloCs = 3
Width = 580 mm
344223
-
3-fold
Number of connections for HeatBloCs = 5
Width = 830 mm
344233
-
Prices excl. VAT • 01/2020 • Printed in Germany
PAW GmbH & Co. KG • 31789 Hameln • Germany • Phone: +49-5151-9856-0 • Fax: +49-5151-9856-98 • info@paw.eu • www.paw.eu
177