37431
-
Low-loss header MVW DN 32 (11⁄4")
for boilers with integrated pump
By means of the conversion kit (item no. 37431), the modular distribution manifolds
get a bypass which connects the flow and return line without causing any resistance
(low-loss header).
It must be considered that the pump of the boiler circuit must deliver a higher flow
rate than the consumer pumps need in total. Otherwise, unwanted circulations occur
on the right or left end of the low-loss header. In that case a hydraulic separator (item
no. 374203 or 374213) must be installed below a distribution manifold.
Please note:
When you plan the system you must already check whether
a low-loss header can be used. In combination with central
heating boilers, hydraulic separators must be installed
below / upstream of a distribution manifold as the boiler
delivers a flow rate with a high temperature difference
(leads to unwanted circulation in low-loss headers).
Low-loss header MVW DN 32 (11⁄4")
Item no.
-
2-fold
Number of connections for HeatBloCs = 3
Width = 600 mm
374223
-
3-fold
Number of connections for HeatBloCs = 5
Width = 850 mm
374233
-