• Heating installations with return flow temperature maintenance for solid
fuel boilers, wood-fired and stove heating systems
• High-efficiency pump
• Control valve with an opening temperature of 50, 55 or 60°C
• 1 thermometer ball valve with a red dial thermometer integrated in the
handle, can be pulled off
• 2 thermometer ball valves with a blue dial thermometer integrated in
the handle, can be pulled off
• Connections DN 20: 3⁄4" int. thread
• Connections DN 25: 1" int. thread
1. The thermal valve shuts off the connection to the buffer tank as long as
the water in the boiler circuit is colder than the opening temperature of
the thermal control valve. The pump circulates the water via the bypass,
the small quantity of water in the boiler circuit can now heat up quickly.
2. When the boiler circuit reaches the opening temperature of the control
valve, the valve reduces the bypass flow rate and opens the buffer tank
circuit. The cold water from the buffer tank return is mixed with the hot
boiler circuit water in the control valve. This leads to an increase of the
return temperature in the boiler circuit to the desired level and avoids
condensation in the boiler.
3. When the buffer tank return temperature is higher than the opening
temperature, the control valve completely shuts off the bypass. Thus,
the water from the buffer tank flows directly into the boiler circuit.
If the boiler output is controlled by the boiler temperature, the boiler
must heat up 20 K above the opening temperature of the return flow
temperature maintenance. Otherwise, the boiler might reduce the output
even before the thermal control valve is completely open.
Separate assembly of the group of fittings in the flow and return.
This version permits an easy isolation of the heat generator without
further shut-off valves. Consider the position of the safety group before
mounting.
• 1 x gasket: DN 20 item no. 2057, DN 25 item no. 2157 1 x screw-in fitting:
DN 20 item no. 2053, DN 25 item no. 2153 1 x pump fitting: DN 20 item
no. 2049, DN 25 item no. 2149
D
N
2
0
Temperatures t
BY
= bypass t
KR
= boiler return
t
PR
= return of the buffer tank t
FIX
= opening
temperature
01/2020 • Printed in Germany