Technical data
Application range
• Domestic hot water preparation operating on the principle of a
flow-type water heater
The CE-conformity of the module has been certified
according to DIN EN 60335 and
SVGW / ACS.
Application range
• in solar thermal systems
• in systems with solid fuel boilers, oil or gas boilers
• connection to a buffer tank
• as double cascade up to 100 l/min (as per SPF LK 1)*
*For information on design data, see page 230
Operating data
Max. pressure
Maximum operating temperature
Min. flow rate
Max. flow rate as per SPF LK 1*
Transmission performance 1 as per SPF LK 1*
Kvs value
primary: 3 bars,
secondary: 10 bars
95 °C
2 l/min
50 l/min
121 kW
primary: 4.1
secondary: 3.4
Equipment
Check valve
Circulation line
Heat exchanger
Sensors
Controllers
primary: 2 x 200 mm wc
optional
40 Plates, Type B25
primary: 1 x Pt1000
secondary: 2 x Pt1000
1 x Flow meter
FC3.10
Nominal diameter
Connections
Circulation line
Width
Centre distance, prim.
Centre distance, sec.
Height
Installation length
Depth
DN 20 (3⁄4")
primary:
11⁄2" external thread
secondary:
1" external thread
1" ext. thread
602 mm
120mm
100mm
795 mm
757 mm
298 mm
Materials
Valves and fittings
Gaskets
Insulation
Heat exchanger
Brass
AFM34/EPDM
EPP
Solder: Copper
Plates + connecting pieces:
Stainless steel
Coating (optional): Based
on silica
Differential pressure diagram
Dimensions
Mounting example
Cascade with 2 basic modules (item no. 6405510) and
pipe set for cascade (item no. 64042942)
F
r
i
w
a
M
i
d
i
01/2020 • Printed in Germany
240
PAW GmbH & Co. KG • 31789 Hameln • Germany • Phone: +49-5151-9856-0 • Fax: +49-5151-9856-98 • info@paw.eu • www.paw.eu