Performance data Tank heat transfer module

Midi DN 20 / Maxi DN 25

Functioning:

If the temperature in the domestic hot water tank (secondary tank)

falls below the nominal temperature set, the charging cycle is started.

If the temperature of the heat source is not sufficient, the potential-

free relay is switched on (depending on the system) for the reheating

demand. If the temperature available on the primary side is not

sufficient, the output of the secondary pump is possibly reduced.

Depending on the temperatures and the flow rate of the secondary

(potable water) side, the primary pump is controlled in such a way

that the adjustable nominal temperature is reached. A relay switching

on simultaneously with the primary or secondary pump enables the

use of a non-return valve or the switching of a 3-way valve (heating

operation / domestic hot water operation).

When using a switch valve it is possible, depending on the primary

return temperature of the station, to stratify the return flow rate in the

primary storage tank in two different levels. An additional relay with

a corresponding PWM outlet allows the connection of a controlled

circulation pump. The circulation pump can be activated depending

on the temperature and the time. Furthermore, the controller

contains a time-dependent disinfection control.

Controller FC4.13

The controller FC4.13 sets the hot water temperature of the tank heat

transfer module via the speed control of the primary pump.

The operation of the return distribution valve is an additional function

of the controller. Different operating modes are possible which

can be adapted to the system requirements. The tank heat transfer

module can be used as preheating station or as storage tank system

with or without buffer tank.

The pumps are actuated via a PWM signal. An output for switching

the return distribution valve is available.

Preset systems:

Tank heat transfer module - Basic system with

return distribution and circulation

01/2020 • Printed in Germany

PAW GmbH & Co. KG • 31789 Hameln • Germany • Phone: +49-5151-9856-0 • Fax: +49-5151-9856-98 • info@paw.eu • www.paw.eu

251

Function overview controller FC4.13

Display

multiline LC-text display,

illuminated, with menu navigation

(multilingual)

Operation

7 push buttons

Relay outputs

3 x semiconductor relays, 230 V

1 x potential-free relay

4 x PWM signal for speed control

Inputs

10 x Pt1000

1 x Impulse input V40

Flow rate sensors

yes

Heat quantity balancing