Application range
• zur Beladung/Vorheizung von Trinkwasserspeichern aus
großen Pufferspeichersystemen bei großen Zapfvolumen
The CE-conformity of the module has been certified
according to DIN EN 60335 and SVGW / ACS.
Application range
• in solar thermal systems
• in systems with solid fuel boilers, oil or gas boilers
• connection to a buffer tank
• up to 33 l/min
Operating data
Max. pressure
Maximum operating temperature
Min. flow rate
Max. flow rate
Transmission performance 1
primary: 3 bars, secondary: 10
bars
2-95 °C
2 l/min
33 l/min
92 kW
Technical data
Equipment
Check valve
Heat exchanger
Sensors
Controllers
primary: 2 x 200 mm wc
40 Plates, Type IC25
3 x Pt1000 (integrated),
3 x Pt1000 (enclosed)
Controller FC4.13
Dimensions
Nominal diameter
Connections
Width
Centre distance, prim.
Centre distance, sec.
Height
Installation length
Depth
DN 20 (3⁄4")
primary: 11⁄2" external thread
secondary: 1" external thread,
flat-sealing
602 mm
120 mm
220 mm
795 mm
757 / 713 mm
298 mm
Materials
Valves and fittings
Gaskets
Insulation
Brass
Flat sealings: AFM34 /
EPDM; o-rings: Klingersil
/ EPDM