• CE conform according to DIN EN 60335
• insulation according to EnEV directive
The solar circuit in a solar thermal system must be filled with a water
and propylene glycol mixture to prevent frost damage. The heating
installation is normally operated with water.
To transfer the heat energy from the solar circuit to the heating circuit,
a heat exchanger is used.
In small systems, a smooth pipe heat exchanger integrated in the
storage tank transfers the heat energy. With larger collector fields, the
heat transfer capacity of those heat exchangers is no longer sufficient.
In large systems, solar transfer stations transfer the collected heat
energy from the collectors to the heating water circuit.
The centre piece of those modules is a plate heat exchanger, which
allows an efficient heat transfer by means of its cross-flow operating
mode.
The operating conditions of the heat exchanger vary due to
fluctuation in heat radiation, buffer temperatures and individual
system requirements. To operate the entire system at its optimum, you
have to set the flow rates at the heat exchanger, depending on the
individual control target and the current conditions.
For this purpose the Solex modules use high-efficiency pumps, which
offer an extremely broad adjustment range.
Thus the controller efficiently adjusts the pumps to the current
required flow rates.
Additionally, the pumps used save more than 50% of electrical driven
energy compared to conventional asynchronous pumps. Furthermore,
these pumps meet the energy efficiency guidelines (EuP / ErP READY)
of 2015.
The controller is delivered preset, mounted and prewired to guarantee
an easy adjustment to the real system.
The use of flow rate sensors in the Solex modules allows a power
adjusted control, an efficient system monitoring and an integrated
heat quantity measurement.
For a safe and quick commissioning, the Solex modules are equipped
with pressure relief valves, ball valves as well as with fill and drain
valves.
262
01/2020 • Printed in Germany
PAW GmbH & Co. KG • 31789 Hameln • Germany • Phone: +49-5151-9856-0 • Fax: +49-5151-9856-98 • info@paw.eu • www.paw.eu
S
o
l
e
x