Equipment
Application range
• for charging domestic hot water tanks
• with heat quantity measurement according to the BAFA
promotion directive for solar thermal systems
The CE-conformity of the installation has been certified
according to DIN EN 60335.
Application range
• up to 200 m2 Collector surface area
For information on design data and solpump performance
data, see page 261 / 264
Technical data
Operating data
Max. pressure
Maximum operating temperature
Operating mode 1
Operating mode 2
primary: 6 bars
secondary: 10 bars
primary: 120 °C
secondary: 95 °C
15 l/(m2xh)
25 l/(m2xh)
Dimensions
Materials
Check valves
Heat exchanger
Controllers
Sensors
FlowRotor (primary)
Pressure gauge
Solar pressure relief valve:
primary: 2 x 200 mm wc
secondary: 1 x 150 mm wc
2 x 50 Plates, Type XB37M
SC5.14
2 x Pt1000 (integrated),
2 x Pt1000 (enclosed)
2-130 l/min
0-6 bars, temperature-
resistant
primary: 6 bars
secondary: 10 bars
Nominal diameter
Connections
Width
Centre distance
Height
Installation length
Depth
DN 32 (11⁄4")
primary: 11⁄2" internal thread
secondary: 11⁄2" external thread
710 mm
158 mm
1654 mm
1175 mm
920 mm
Valves and fittings
Gaskets
Insulation
Check valves
Heat exchanger
Brass/Bronze
EPDM or AFM 34,
asbestos-free
EPP
Brass
Solder: 99.99 % copper
Plates + connecting
pieces: 1.4401 (AISI 316)
SolexMega TW - DN 32 (11⁄4")
Item no.
€ / piece
-
Accessories
prim.: Grundfos UPMXL 25-125, sec.: Grundfos UPML 25-105 N
2-way zone valve - DN 25 (1"), suitable for DHW
suitable for DHW, for connecting or disconnecting single storage tanks or flow paths,
DN 25, 1" internal thread, setting time 90°: 12 sec, Kvs value = 60.
DVGW, ACS and WRAS certified.
6097465
563551
-
.
S
o
l
e
x
M
e
g
a
T
W
Prices excl. VAT • 01/2020 • Printed in Germany
282
PAW GmbH & Co. KG • 31789 Hameln • Germany • Phone: +49-5151-9856-0 • Fax: +49-5151-9856-98 • info@paw.eu • www.paw.eu