HP
Unità esterna
Alimentazione
Tensione
Fase
Frequenza
V
Hz
18 HP
U-8ME2E8
U-10ME2E8
380-400-415
3ph
50
20 HP
U-10ME2E8
U-10ME2E8
380-400-415
3ph
50
2,00
80
448
59,0
56,0
80,0
1842x1600
x1000/420
5/8 (15,88) /
3/4 (19,05)
1-1/8 (28,58) /
1-1/4 (31,75)
1/4 (6,35)
11,20 / 23,3856
50~130(200)
-10~+52
-25~+18
32 HP
22 HP
U-10ME2E8
U-12ME2E8
380-400-415
3ph
50
2,00
80
456
61,0
58,0
82,0
1842x2010
x1000/480
5/8 (15,88) /
3/4 (19,05)
1-1/8 (28,58) /
1-1/4 (31,75)
1/4 (6,35)
13,90 / 29,0232
50~130(200)
-10~+52
-25~+18
34 HP
24 HP
U-12ME2E8
U-12ME2E8
380-400-415
3ph
50
2,00
80
464
62,0
59,0
83,0
1842x2420
x1000/540
5/8 (15,88) /
3/4 (19,05)
1-1/8 (28,58) /
1-1/4 (31,75)
1/4 (6,35)
16,60 / 34,6608
50~130(200)
-10~+52
-25~+18
36 HP
26 HP
U-10ME2E8
U-16ME2E8
380-400-415
3ph
50
3,00
80
456
62,5
59,5
83,5
1842x2010
x1000/535
3/4 (19,05) /
7/8 (22,22)
1-1/4 (31,75) /
1-1/2 (38,10)
1/4 (6,35)
13,90 / 29,0232
50~130(200)
-10~+52
-25~+18
38 HP
28 HP
U-12ME2E8
U-16ME2E8
380-400-415
3ph
50
3,00
80
464
63,5
60,5
84,5
1842x2420
x1000/585
3/4 (19,05) /
7/8 (22,22)
1-1/4 (31,75) /
1-1/2 (38,10)
1/4 (6,35)
16,60 / 34,6608
50~130(200)
-10~+52
-25~+18
40 HP
U-12ME2E8
U-12ME2E8
U-16ME2E8
380-400-415
3ph
50
4,00
80
696
64,5
61,5
85,5
1842 x 3660
x1000/855
3/4 (19,05) /
7/8 (22,22)
1-1/2 (38,10) /
1-5/8 (41,28)
1/4 (6,35)
24,90 / 46,3536
50~130(200)
-10~+52
-25 ~ +18
Capacità di raffresc.
kW
50,0
56,0
61,5
68,0
73,0
78,5
EER
1)
W/W
4,55
4,38
4,13
3,93
3,80
3,69
Corrente
A
18,20 - 17,30 - 16,60
21,40 - 20,30 - 19,60
24,30 - 23,10 - 22,30
28,00 - 26,60 - 25,60
31,70 - 30,10 - 29,00
34,80 - 33,10 - 31,90
Potenza d'ingresso
kW
11,00
12,80
14,90
17,30
19,20
21,30
Capacità di riscald.
kW
56,0
63,0
69,0
76,5
81,5
87,5
COP
1)
W/W
4,96
4,77
4,76
4,69
4,55
4,56
Corrente
A
18,70 - 17,70 - 17,10
22,00 - 20,90 - 20,20
23,90 - 22,70 - 21,90
26,60 - 25,30 - 24,40
29,90 - 28,40 - 27,40
31,70 - 30,10 - 29,00
Potenza d'ingresso
kW
11,30
13,20
14,50
16,30
17,90
19,20
Corrente di avviamento
Pressione statica esterna (max.)
A
2,00
Pa
80
m3/min
448
dB(A)
58,5
dB(A)
55,5
dB(A)
79,5
Portata d'aria
Pressione sonora
Potenza sonora
Dimensioni /
Peso netto
Diametro delle
tubazioni
2)
Normale
Modalità silenziosa
Modalità normale
A xL xP
Liquido
Gas
Bilanciamento
mm / kg
Pollici (mm)
Pollici (mm)
Pollici (mm)
1842x1600
x1000/420
5/8 (15,88) /
3/4 (19,05)
1-1/8 (28,58) /
1-1/4 (31,75)
1/4 (6,35)
11,20 / 23,3856
50~130(200)
-10~+52
-25~+18
30 HP
Refrigerante (R410A) / CO
2
Eq.
Rapporto di capacità interna/esterna
massimo consentito
3)
kg
%
°C
°C
V
Hz
A
Pa
/T
Campo di
funzionamento
HP
Unità esterna
Alimentazione
Raffresc. Min ~ Max
Riscald. Min ~ Max
Tensione
Fase
Frequenza
U-14ME2E8
U-16ME2E8
U-16ME2E8
U-16ME2E8
U-10ME2E8
U-12ME2E8
U-10ME2E8
U-12ME2E8
U-12ME2E8
U-12ME2E8
U-12ME2E8
U-12ME2E8
U-16ME2E8
Capacità di raffresc.
kW
85,0
90,0
96,0
101,0
107,0
113,0
EER
1)
W/W
3,68
3,52
4,05
3,95
3,84
3,75
Corrente
A
38,60 - 36,60 - 35,30
42,30 - 40,20 - 38,70
38,70 - 36,80 - 35,50
41,40 - 39,30 - 37,90
46,10 - 43,80 - 42,20
49,20 - 46,70 - 45,00
Potenza d'ingresso
kW
23,10
25,60
23,70
25,60
27,90
30,10
Capacità di riscald.
kW
95,0
100,0
108,0
113,0
119,0
127,0
COP
1)
W/W
4,48
4,42
4,72
4,73
4,61
4,57
Corrente
A
35,40 - 33,60 - 32,40
37,70 - 35,80 - 34,60
37,80 - 35,90 - 34,60
39,00 - 37,10 - 35,80
42,60 - 40,50 - 39,00
45,90 - 43,60 - 42,00
Potenza d'ingresso
kW
21,20
22,60
22,90
23,90
25,80
27,80
Corrente di avviamento
Pressione statica esterna (max.)
380-400-415
3ph
50
4,00
80
464
63,5
60,5
84,5
1842 x 2420
x1000/630
3/4 (19,05) /
7/8 (22,22)
1-1/4 (31,75) /
1-1/2 (38,10)
1/4 (6,35)
16,60 / 34,6608
50~130(200)
-10~+52
-25 ~ +18
380-400-415
3ph
50
4,00
80
464
64,0
61,0
85,0
1842 x 2420
x1000/630
3/4 (19,05) /
7/8 (22,22)
1-1/4 (31,75) /
1-1/2 (38,10)
1/4 (6,35)
16,60 / 34,6608
50~130(200)
-10~+52
-25 ~ +18
380-400-415
3ph
50
3,00
80
688
63,0
60,0
84,0
1842 x 3250
x1000/750
3/4 (19,05) /
7/8 (22,22)
1-1/4 (31,75) /
1-1/2 (38,10)
1/4 (6,35)
22,20 / 46,3536
50~130(200)
-10~+52
-25 ~ +18
380-400-415
3ph
50
3,00
80
696
64,0
61,0
85,0
1842 x 3660
x1000/810
3/4 (19,05) /
7/8 (22,22)
1-1/2 (38,10) /
1-5/8 (41,28)
1/4 (6,35)
24,90 / 51,9912
50~130(200)
-10~+52
-25 ~ +18
380-400-415
3ph
50
4,00
80
688
64,0
61,0
85,0
1842 x 3250
x1000/795
3/4 (19,05) /
7/8 (22,22)
1-1/2 (38,10) /
1-5/8 (41,28)
1/4 (6,35)
22,20 / 46,3536
50~130(200)
-10~+52
-25 ~ +18
Portata d'aria
Pressione sonora
Potenza sonora
Dimensioni /
Peso netto
Diametro delle
tubazioni
2)
Normale
Modalità silenziosa
Modalità normale
A xL xP
Liquido
Gas
Bilanciamento
m3/min
dB(A)
dB(A)
dB(A)
mm / kg
Pollici (mm)
Pollici (mm)
Pollici (mm)
kg / T
%
°C
°C
Refrigerante (R410A) / CO
2
Eq.
Rapporto di capacità interna/esterna
massimo consentito
3)
Campo di
Raffresc. Min ~ Max
funzionamento
Riscald. Min ~ Max
56
I dati sono indicativi. 1) Il calcolo di EER e COP è basato sulla norma EN14511. 2) Diametro delle tubazioni inferiore a 90 m per l'unità interna finale / superiore a 90 m per l'unità interna finale (se la lunghezza
equivalente delle tubazioni supera i 90 m, aumentare le dimensioni dei tubi principali di 1 livello per i tubi del gas e i tubi del liquido). 3) Se sono soddisfatte le seguenti condizioni, l'intervallo effettivo è
superiore al 130% e inferiore al 200%: A. Rispettare il numero limite di unit
à interne collegabili. B. Il limite inferiore del campo di funzionamento per la temperatura esterna di riscaldamento è limitato a -10 °C
B.U. (standard -25 °C B.U.). C. Il funzionamento simultaneo
è limitato a meno del 130% delle unità interne collegabili.