R410A

INDICE GENERALE

Serie ECOi EX ME2 a 2 tubi, combinazione di modelli salvaspazio da 22 a 80 HP

HP

Unità esterna

Alimentazione

22 HP

U-10ME2E8

U-12ME2E8

380-400-415

3ph

50

2,00

80

456

dB(A)

dB(A)

82,0

83,0

83,5

84,5

84,5

85,0

84,0

Tensione

Fase

Frequenza

V

Hz

A

Pa

m3/min

24 HP

U-12ME2E8

U-12ME2E8

380-400-415

3ph

50

2,00

80

464

26 HP

U-10ME2E8

U-16ME2E8

380-400-415

3ph

50

3,00

80

456

28 HP

U-12ME2E8

U-16ME2E8

380-400-415

3ph

50

3,00

80

464

30 HP

U-14ME2E8

U-16ME2E8

380-400-415

3ph

50

4,00

80

464

32 HP

U-16ME2E8

U-16ME2E8

380-400-415

3ph

50

4,00

80

464

34 HP

U-14ME2E8

U-20ME2E8

380-400-415

3ph

50

4,00

80

637

Capacità di raffresc.

kW

61,5

68,0

73,0

78,5

85,0

90,0

96,0

EER

1)

W/W

4,13

3,93

3,80

3,69

3,68

3,52

3,56

SEER

2)

6,90

6,86

6,62

6,60

6,88

6,55

7,21

Corrente

A

24,30 - 23,10 -

22,30

28,00 - 26,60 -

25,60

31,70 - 30,10 -

29,00

34,80 - 33,10 -

31,90

38,60 - 36,60 -

35,30

42,30 - 40,20 -

38,70

44,10 - 41,90 -

40,40

Potenza d'ingresso

kW

14,90

17,30

19,20

21,30

23,10

25,60

27,00

Capacità di riscald.

kW

69,0

76,5

81,5

87,5

95,0

100,0

108,0

COP

1)

W/W

4,76

4,69

4,55

4,56

4,48

4,42

4,17

SCOP

2)

4,53

4,78

4,16

4,29

4,13

4,09

4,14

Corrente

A

23,90 - 22,70 -

21,90

26,60 - 25,30 -

24,40

29,90 - 28,40 -

27,40

31,70 - 30,10 -

29,00

35,40 - 33,60 -

32,40

37,70 - 35,80 -

34,60

42,80 - 40,60 -

39,20

Potenza d'ingresso

kW

14,50

16,30

17,90

19,20

21,20

22,60

25,90

Corrente di avviamento

Pressione statica esterna (max.)

Portata d'aria

Pressione sonora

Potenza sonora

Dimensioni /

Peso netto

Diametro delle

tubazioni

3)

Modalità normale /

silenziosa

Modalità normale

A xL xP

Liquido

Gas

61,0 / 58,0

62,0 / 59,0

62,5 / 59,5

63,5 / 60,5

63,5 / 60,5

64,0 / 61,0

63,0 / 60,0

Bilanciamento

Refrigerante (R410A) / CO

2

Eq.

Rapporto di capacità interna/esterna

mm / kg

Pollici (mm)

Pollici (mm)

Pollici (mm)

kg / T

%

°C

°C

V

Hz

A

Pa

m3/min

dB(A)

dB(A)

mm / kg

Pollici (mm)

Pollici (mm)

Pollici (mm)

kg / T

%

°C

°C

1842x2010

x1000/480

5/8 (15,88) /

3/4 (19,05)

1-1/8 (28,58) /

1-1/4 (31,75)

1/4 (6,35)

13,90 / 23,3856

50~130(200)

-10~+52

-25~+18

36 HP

U-16ME2E8

U-20ME2E8

380-400-415

3ph

50

4,00

80

637

63,5 / 60,5

84,5

1842 x 2780

x1000/690

3/4 (19,05) /

7/8 (22,22)

1-1/2 (38,10) /

1-5/8 (41,28)

1/4 (6,35)

17,80 / 37,1664

50~130(200)

-10~+52

-25~+18

1842x2420

x1000/540

5/8 (15,88) /

3/4 (19,05)

1-1/8 (28,58) /

1-1/4 (31,75)

1/4 (6,35)

16,60 / 34,6608

50~130(200)

-10~+52

-25~+18

38 HP

U-18ME2E8

U-20ME2E8

380-400-415

3ph

50

4,00

80

810

62,5 / 59,5

83,5

1842 x 3140

x1000/750

3/4 (19,05) /

7/8 (22,22)

1-1/2 (38,10) /

1-5/8 (41,28)

1/4 (6,35)

19,00 / 39.672

50~130(200)

-10~+52

-25~+18

1842x2010

x1000/525

3/4 (19,05) /

7/8 (22,22)

1-1/4 (31,75) /

1-1/2 (38,10)

1/4 (6,35)

13,90 / 29,0232

50~130(200)

-10~+52

-25~+18

40 HP

U-20ME2E8

U-20ME2E8

380-400-415

3ph

50

4,00

80

810

63,0 / 60,0

84,0

1842 x 3140

x1000/750

3/4 (19,05) /

7/8 (22,22)

1-1/2 (38,10) /

1-5/8 (41,28)

1/4 (6,35)

19,00 / 39.672

50~130(200)

-10~+52

-25~+18

1842x2420

x1000/585

3/4 (19,05) /

7/8 (22,22)

1-1/4 (31,75) /

1-1/2 (38,10)

1/4 (6,35)

16,60 / 34,6608

50~130(200)

-10~+52

-25~+18

42 HP

U-10ME2E8

U-16ME2E8

U-16ME2E8

380-400-415

3ph

50

5,00

80

688

65,0 / 62,0

86,0

1842 x 3250

x1000/840

3/4 (19,05) /

7/8 (22,22)

1-1/2 (38,10) /

1-5/8 (41,28)

1/4 (6,35)

22,20 / 46,3536

50~130(200)

-10~+52

-25~+18

1842x2420

x1000/630

3/4 (19,05) /

7/8 (22,22)

1-1/4 (31,75) /

1-1/2 (38,10)

1/4 (6,35)

16,60 / 34,6608

50~130(200)

-10~+52

-25~+18

44 HP

U-12ME2E8

U-16ME2E8

U-16ME2E8

380-400-415

3ph

50

5,00

80

696

65,5 / 62,5

86,5

1842 x 3660

x1000/900

3/4 (19,05) /

7/8 (22,22)

1-1/2 (38,10) /

1-5/8 (41,28)

1/4 (6,35)

24,90 / 51,9912

50~130(200)

-10~+52

-25~+18

1842x2420

x1000/630

3/4 (19,05) /

7/8 (22,22)

1-1/4 (31,75) /

1-1/2 (38,10)

1/4 (6,35)

16,60 / 34,6608

50~130(200)

-10~+52

-25~+18

46 HP

U-14ME2E8

U-16ME2E8

U-16ME2E8

380-400-415

3ph

50

6,00

80

696

65,5 / 62,5

86,5

1842 x 3660

x1000/945

3/4 (19,05) /

7/8 (22,22)

1-1/2 (38,10) /

1-5/8 (41,28)

1/4 (6,35)

24,90 / 51,9912

50~130(200)

-10~+52

-25~+18

1842x2780

x1000/690

3/4 (19,05) /

7/8 (22,22)

1-1/4 (31,75) /

1-1/2 (38,10)

1/4 (6,35)

17,80 / 37,1664

50~130(200)

-10~+52

-25~+18

48 HP

U-16ME2E8

U-16ME2E8

U-16ME2E8

380-400-415

3ph

50

6,00

80

696

66,0 / 63,0

87,0

1842 x 3660

x1000/945

3/4 (19,05) /

7/8 (22,22)

1-1/2 (38,10) /

1-5/8 (41,28)

1/4 (6,35)

24,90 / 51,9912

50~130(200)

-10~+52

-25~+18

massimo consentito

4)

Campo di

funzionamento

HP

Unità esterna

Alimentazione

Raffresc. Min ~ Max

Riscald. Min ~ Max

Tensione

Fase

Frequenza

Capacità di raffresc.

kW

101,0

107,0

113,0

118,0

124,0

130,0

135,0

EER

1)

W/W

3,42

3,42

3,34

3,69

3,62

3,62

3,52

SEER

2)

6,86

7,32

7,16

6,57

6,60

6,70

6,55

Corrente

A

47,70 - 45,30 -

43,70

50,60 - 48,10 -

46,30

54,10 - 51,40 -

49,50

52,80 - 50,20 -

48,40

56,00 - 53,20 -

51,30

59,90 - 56,90 -

54,90

63,40 - 60,20 -

58,10

Potenza d'ingresso

kW

25,9

31,3

33,8

32,0

34,3

35,9

38,4

Capacità di riscald.

kW

113,0

119,0

127,0

132,0

138,0

145,0

150,0

COP

1)

W/W

4,14

4,13

3,92

4,49

4,50

4,46

4,42

SCOP

2)

4,06

4,14

4,13

4,11

4,21

4,12

4,09

Corrente

A

44,60 - 42,40 -

40,80

47,10 - 44,70 -

43,10

52,40 - 49,80 -

48,00

49,10 - 46,60 -

44,90

50,70 - 48,20 -

46,40

54,30 - 51,50 -

49,7

56,60 - 53,80 -

51,8

Potenza d'ingresso

kW

27,30

28,80

32,40

29,40

30,70

32,50

33,90

Corrente di avviamento

Pressione statica esterna (max.)

Portata d'aria

Pressione sonora

Potenza sonora

Dimensioni /

Peso netto

Diametro delle

tubazioni

3)

Modalità normale /

silenziosa

Modalità normale

A xL xP

Liquido

Gas

Bilanciamento

Refrigerante (R410A) / CO

2

Eq.

Rapporto di capacità interna/esterna

massimo consentito

4)

Campo di

Raffresc. Min ~ Max

funzionamento

Riscald. Min ~ Max

58

1) Il calcolo di EER e COP è basato sulla norma EN14511. 2) I valori SEER / SCOP sono calcolati in base ai valori di efficienza stagionale di raffrescamento/riscaldamento degli ambienti “η” del REGOLAMENTO

DELLA COMMISSIONE (UE) 2016/2281. SEER, SCOP = (η + Correzione) × PEF. 3) Diametro delle tubazioni inferiore a 90 m per l'unità interna finale / superiore a 90 m per l'unità interna finale (se la lunghezza

equivalente delle tubazioni supera i 90 m, aumentare le dimensioni dei tubi principali di 1 livello per i tubi del gas e i tubi del liquido). 4) Se sono soddisfatte le seguenti condizioni, l'intervallo effettivo è

superiore al 130% e inferiore al 200%: A. Rispettare il numero limite di unit

à interne collegabili. B. Il limite inferiore del campo di funzionamento per la temperatura esterna di riscaldamento è limitato a -10 °C

B.U. (standard -25 °C B.U.). C. Il funzionamento simultaneo

è limitato a meno del 130% delle unità interne collegabili.